Who this guide is for
- Anyone choosing or changing a roof covering on a new or existing roof
- Renovators comparing quotations that describe the covering but not the layers beneath it
- Self-builders coordinating a roofer with whoever is designing the build-up
- Owners trying to understand what an underlay is actually doing on their roof
- Readers briefing a designer who has offered more than one covering option
Lapped or continuous: an observation you can make from the ground
The tile and slate record gives the test directly. A lapped covering shows repeating open joints that rely on overlap and gravity, and a seamed metal roof shows continuous trays whose joints are folded shut. That single observation, the record says, explains why one type carries a genuine secondary drainage plane beneath it and the other does not need one in the same sense.
It is worth making that observation before any other question is asked, because almost everything else follows from it. The way each family sheds water decides what has to exist underneath, what that layer has to be able to do, and which trade has to have been thinking about it while the roof was being built.
- Repeating open joints: water is expected to pass and has to be caught
- Folded continuous seams: the joint stands above the drainage surface
- A bonded panel: the field has no site-formed joint at all
- A profiled twin-skin roof: the layers are separate and fixed one at a time
What a lapped covering requires beneath it
A covering of overlapping units sheds most of the water and expects the rest to be handled. The record describes the underlay as a drainage plane rather than a waterproofing layer, whose purpose is to catch what the covering lets through, including wind-driven rain, snow entry, condensate and debris, and carry it out at the eaves. The difference between those two descriptions shows up wherever the underlay is trimmed short, punctured, or lapped against the direction of flow.
That plane only works if water reaching it can keep moving. Where the underlay is draped between rafters, the sag below the batten line is the channel water runs in. Where it is laid over a continuous deck or sarking there is no drape, the batten bears along its whole length and each crossing becomes a small dam, so a counter-batten is what restores a drainage path and an air space above the sheet. The published junction record calls that crossing the point at which the path is either created or absent, concealed for the roof's whole life.
And what it requires at the edge
The underlay only works if it stays continuous to the outside. Where it is cut back behind a gutter, stopped short at a valley, or lapped against the flow, water that the covering handed over correctly is delivered into the structure instead of out of it, and the record notes that the symptom looks like a covering problem and is not one.
The eaves junction record describes the same requirement from the other side: water leaving the roof has to be delivered into the gutter, far enough out that it clears the fascia and with the underlay behind it discharging into the gutter rather than behind it. When that goes wrong, the damage appears on the fascia, on the wall or at the base of the wall rather than at the roof.
What a continuous covering asks for instead
A standing seam roof asks for different things and asks for them firmly. The record states that everything the metal sits on is chosen with the covering's behaviour in mind: the deck has to be continuous, even and dry enough to receive clips and to avoid telegraphing its irregularities into a reflective surface, and the separation layer between metal and deck manages contact, abrasion and incidental water. A depression in the deck becomes a visible dish, a proud fastener becomes a wear point as the tray slides, and a deck closed in wet condition releases moisture upward into the interface where it has no easy route out.
The other requirement is inboard rather than outboard. Because the covering is thin, conductive and impermeable, it runs cold on clear nights, so the record treats the continuity of the air and vapour control layers below the deck as mattering more here than under a covering that can breathe through its joints. That is a requirement on the build-up, arriving from a decision about the visible surface.
- A continuous deck the clips can be fastened into across the whole roof
- A separation layer between a moving covering and a deck that does not move
- A deck whose moisture condition at the time of covering has been considered
- Air and vapour control below the deck, continued into the walls
A bonded panel moves the requirement into its joints
A composite panel roof carries weathering, insulating and lining duties in one component, and the record observes that there is remarkably little to discuss about the field as a result. Design attention moves outward to the longitudinal joint, the end joint, the fixings and every point where a panel abuts something that is not a panel. Within the panel the liner face closes the air path without any site-formed lap, which is why the joints between panels carry that duty entirely.
A built-up twin-skin roof answers the same brief in the opposite way. There the liner sheet is the air and vapour control element as well as the visible ceiling, so its sealed side laps, end laps and closed perimeter are what the assembly depends on. The record notes that a liner which looks faultless from below and is open at its side laps has failed at the duty that matters, and the symptom appears later, inside the build-up.
Why neither page can say this
The covering entries state that the build-up beneath is somebody else's subject, and they are right to: the same tiles can sit over a ventilated cold roof, over insulation held between and under rafters, or over a warm deck, and nothing about the units settles that. The build-up entries state the converse, that the covering is chosen separately. Read singly, each is a complete and accurate account of one thing.
Read together, they describe a dependency that neither is permitted to assert. A covering choice is also a decision about whether a secondary drainage plane is needed, whether a counter-batten path has to exist, whether a continuous deck is required, and where the air and vapour control lines have to be. Asking that question at the point the covering is chosen is cheaper than discovering it when the battens are being ordered.
What to ask when a covering is being chosen
The useful questions are about the layers rather than the units. The tile and slate record asks what secondary drainage path is assumed at underlay level and where exactly it discharges, whether a counter-batten void is part of the build-up and, if it is not, what takes over its function, and whether the build-up beneath relies on air paths the covering arrangement has to keep open. The standing seam record asks whether the chosen deck can receive clips across the whole roof including at the perimeter zones, and which vapour and air control layers sit below the deck.
Both records also ask about metals, and the question is the same in each case: which metals will sit in contact at fixings, flashings and rainwater goods, and which metals will the run-off from this roof pass over before it leaves the building. Compatibility along the whole drainage path is described as part of the design rather than a site decision.
What to establish when a covering is chosen or changed
- 1Establish whether the covering sheds by overlap or by a continuous folded or bonded surface
- 2Ask what secondary drainage path is assumed beneath the covering, if any
- 3Ask where that path discharges, and whether it clears the gutter and the wall head
- 4Establish whether a counter-batten void is part of the build-up, and what replaces it if not
- 5Ask whether the underlay is intended to be open or closed to vapour, and what that assumes elsewhere
- 6Ask whether a continuous deck is required, and whether the chosen deck can receive the fixings
- 7Ask what separation sits between a moving covering and the deck beneath it
- 8Establish where the air and vapour control layers sit relative to the deck
- 9Ask whether the build-up below relies on air paths the covering has to keep open
- 10Establish which metals will be in contact at fixings, flashings and rainwater goods
- 11Ask which metals the run-off will pass over before it leaves the building
- 12Ask who is coordinating the covering with whoever is designing the build-up
Common mistakes to avoid
- Reading the underlay as a waterproof layer, when it is a drainage plane carrying water back out
- Laying tile battens straight onto a fully supported underlay so each crossing becomes a small dam
- Trimming the underlay short behind a gutter, so water the covering handed over is delivered inward
- Treating a continuous metal covering as though it needed the same underlay as a lapped one
- Assuming a bonded panel roof has no detailing, when the difficulty has moved into the joints
- Judging a twin-skin liner on how it looks from below rather than on whether its laps are sealed
- Choosing a covering and only then asking what the layers beneath it have to do
When to involve a professional
- Ask the roof designer to show the covering, the underlay, the battens and any air path together on one section
- Ask what the underlay is assumed to be doing, and whether ventilation elsewhere in the roof is being relied on
- Ask what the deck has to deliver for the chosen covering, including its moisture condition at the time of covering
- Ask where the air and vapour control layers run and how they continue into the walls
- Ask who is confirming compatibility between the fixings, the flashings and the rainwater goods
Frequently asked questions
Questions readers ask about this topic
Is the underlay under my tiles keeping water out?
The record describes it as a secondary drainage plane rather than a waterproofing layer. Its purpose is to catch what the covering lets through and carry it out at the eaves, so it is not being asked to be the primary defence, and the difference shows wherever it is trimmed short, punctured or lapped against the direction of flow.
What is a counter-batten actually for?
It lifts the tile battens clear of the underlay so water can travel freely beneath them and air can move behind the covering. The record notes it matters most where the underlay is fully supported, because there the sheet has no drape of its own to drain through and each batten crossing would otherwise hold water along its whole length.
Does a metal roof need an underlay in the same way?
A seamed metal roof is a continuous covering rather than a lapped one, and the record describes what it needs differently: a continuous supporting deck, a separation layer managing contact, abrasion and incidental water, and continuity of the air and vapour control layers below the deck, because the underside of thin metal is a preferred condensation surface.
Can I change the covering without changing anything underneath?
The records treat that as unlikely rather than impossible. A change of unit weight or fixing method reaches back into the battens, the structure and the wind restraint, and a change between a lapped and a continuous family changes what has to exist beneath the covering entirely. What a specific roof can accept is a design determination.
Who is responsible for the layers between the covering and the structure?
That is worth establishing explicitly, because the published records describe the covering and the build-up as separate subjects with separate owners. Where nobody has been asked to reconcile them, the underlay, the batten arrangement and any air path tend to be settled by whoever installs them rather than by anyone who has read both.
Keep reading